Продукция
Главная / Продукция

Вакуумная дугогасительная камера 61179A(38КВ/800A-20КA)

Компания BOV может производить и поставить вакуумные камеры с 12кВ до 126кВ. Продукты широко и успешно применяются в вакуумных выключателях,в выключателях нагрузки,в переключателях электрификации железных дорог и в контакторах.

主要技术参数(断路器用)MAIN TECHNICA DATA(FOR CIRCUIT BREAKER)

额定电压 Rated voltage

38KV

额定电流 Rated current

800A

额定频率 Rated frequency

50/60HZ

额定短时(1min)工频耐受电压Rated Short-time(1min) power-frequency withstand voltage

*85KV

额定雷电冲击耐受电压(峰值)Rated Lightning impulse withstand voltage(peak)

*185KV

额定短路开断电流 Rated short-circuit breaking current

20KA

额定短路开断电流开断次数Operations of short-circuit breaking current interruption

30次

最大直流分量 Max.DC-component

50%

额定短路关合电流 Rated short-circuit making current

50KA

额定峰值耐受电流 Rated peak withstand current

50KA

额定短时耐受电流(4秒) Rated short-time withstand current(4s)

20KA

额定单个电容器组开断电流 Rated breaking current of single capacitor bank

#630A

额定背对背电容器开断电流 Rated breaking current of back to back capacitor bank

#400A

额定触头压力下限时的回路电阻 Circuit resistance at minimum added force

≤25μΩ

机械寿命 Mechanical life

10000次

触头自闭力 Closing force due to bellows and atmosphere

100±30N

额定开距下的触头反力 Force required to hold contacts open at full stroke

200±30N

触头允许磨损厚度 Contact erosion limit

3mm

贮存期 Shelf life

20年

动触头导向套耐受温度 Temperature endurance of lead bushing of moving

170℃

质量/动触头质量 Total mass of interrupter/Moving mass of interrupter

2.18Kg/0.62Kg

额定操作顺序 Rated operating sequence

O-0.3s-CO-180s-CO

配套真空开关的机械参数(建议值)MECHANICAL DATA OF CIRCUIT-BREAKING RECOMMENDATIONS WITH THE INTERRUPTERS

触头开距 Rated contact stroke

14±0.5mm

触头接触行程 Contact connection stroke

4±1mm

平均分闸速度(0-6mm行程) Average opening speed(0-6mm stroke)

1.6±0.2m/s

平均合闸速度(6mm-触头闭合) Average closing speed(6mm-contact making)

0.8±0.2m/s

触头初压力 Added external contact force at contact touch point

≥1100N

额定触头压力 Added force on closed contacts

1800±200N

触头合闸弹跳时间 Max.bouncing duration

≤3ms

触头分合闸不同期 Out of simultaneity of contact closing and opening

≤2ms

分闸触头反弹幅值 Max. rebound distance

≤1mm

分闸触头过冲幅值 Max. overtravel

≤2mm

 

备注(Note):

# 订货时需与BOV公司协商(Must consult with BOV);

* 须有外绝缘保护(With insulation cover);